Two-wire 4–20 mA loop-powered transmitters operate against two opposite electrical cliffs. At the upper NAMUR NE43 alarm state (22 mA), receiver, cable, and intrinsic-safety barrier drops squeeze the terminal voltage left for the transmitter IC. At the lower alarm state (3.6 mA), every microamp drawn by the sensor bridge, analog-to-digital converter (ADC), voltage reference, and regulator must fit inside the minimum loop current.
Calculating both worst-case limits before freezing a bill of materials (BOM) prevents field failures where a transmitter passes a 24 V bench checkout with a short jumper yet clips or loses regulation over a long plant cable run during a supply sag.
How much compliance voltage does a two-wire transmitter require at brownout?
A two-wire transmitter requires its minimum terminal operating voltage (V_DROP_TX) to remain available across the transmitter pins after subtracting all series voltage drops at maximum fault current (I_MAX) and minimum supply voltage (V_LOOP_MIN). The compliance boundary is:
V_LOOP_MIN >= V_DROP_TX + I_MAX × (R_SENSE + R_WIRE + R_BARRIER)
Expressed as available compliance headroom:
V_MARGIN = V_LOOP_MIN − V_DROP_TX − I_MAX × (R_SENSE + R_WIRE + R_BARRIER)
Every term must reflect worst-case field corners rather than nominal bench values: V_LOOP_MIN includes -20% industrial supply brownout tolerance (19.2 V on a 24 V rail), I_MAX uses the 22 mA NAMUR NE43 high-alarm level rather than 20 mA, R_WIRE spans both outward and return conductors at maximum ambient copper temperature, and R_BARRIER accounts for intrinsic-safety Zener barrier series resistance plus any reverse-polarity diode drop.
Consider a realistic hazardous-area industrial loop using a 24 V nominal supply at -20% brownout (19.2 V), a 250 Ω PLC sense resistor (R_SENSE), 100 Ω round-trip field wiring (R_WIRE), and a 300 Ω Zener barrier (R_BARRIER) operating at I_MAX = 22 mA:
- Total series loop resistance:
250 Ω + 100 Ω + 300 Ω = 650 Ω - Total series load drop at 22 mA:
0.022 A × 650 Ω = 14.3 V - Voltage remaining at transmitter terminals:
19.2 V − 14.3 V = 4.9 V - Pass/fail against
V_DROP_TX = 7.5 V(minimum operating supply on TI’s XTR115/XTR116/XTR117 family, including XTR117AIDRBR):4.9 V − 7.5 V = −2.6 V(FAIL).

Even tightening the power-supply tolerance to -10% (21.6 V) leaves 21.6 V − 14.3 V = 7.3 V, still 0.2 V short of the 7.5 V threshold before adding a 0.7 V reverse-polarity protection diode. Bringing this loop into compliance requires a concrete architectural change: dropping R_SENSE from 250 Ω to 100 Ω reduces load drop to 11.0 V (8.2 V at transmitter terminals, +0.7 V margin at 19.2 V), or replacing the passive 300 Ω Zener barrier with a lower-impedance galvanic isolator recovers 4–6 V of compliance headroom.
Why does the 3.6 mA NAMUR NE43 floor cap two-wire sensor power?
Because a two-wire transmitter draws its entire operating energy from the loop current itself, the sum of transmitter quiescent current, sensor excitation, precision reference, ADC, and microcontroller currents must stay strictly below the lowest commanded loop current—typically 3.6 mA (or 3.2 mA on strict NAMUR NE43 low-alarm profiles).
Once local circuitry consumes more than the commanded loop output, the current-control loop saturates at the floor of local demand and loses linearity at the bottom of the scale. As detailed in Analog Devices’ loop-powered transmitter power-budget guide, every sub-circuit must be budgeted at the loop side of its voltage regulator:
- Linear regulator path: Output load current reflects 1:1 onto the loop plus regulator quiescent current (
I_LOOP_LOCAL = I_LOAD + I_Q_REG). - Buck converter path: High-voltage step-down regulators trade voltage headroom for extra local current (
I_LOOP_LOCAL = (V_OUT × I_LOAD) / (η × V_TX)), but startup inrush and switching ripple must be damped so they do not perturb loop regulation or fail HART impedance masks.
Allocate a hard ≤ 3.2 mA active budget when targeting a 3.6 mA low-alarm ceiling, reserving 0.4 mA for temperature drift, component tolerance, and transmitter IC overhead (~0.2 mA quiescent on XTR117). If a heated catalytic sensor, high-excitation RTD bridge, or wireless module pushes continuous draw above 3.2 mA, duty-cycling only succeeds if bulk capacitance absorbs peak bursts without dropping V_REG or injecting current spikes onto the loop; otherwise, the design belongs on a three-wire or four-wire transmitter.
Two-wire IRET transmitters versus three-wire current-output DACs
Swapping between transmitter ICs—or moving from two-wire to three-wire topologies—changes the current-return node, integrated reference scaling, and voltage compliance limits.
| Architecture & reference device | Loop wiring | Supply / compliance range | Local power & return rule | Primary selection trigger |
|---|---|---|---|---|
XTR117AIDRBR (XTR115/116/117 class) |
2-wire loop-powered | 7.5 V to 40 V (36 V on XTR115/116) |
All local electronics must return to IRET; total current < 3.6 mA |
Field sensors powered strictly from the 24 V loop |
| AD5420AREZ | 3-wire / 4-wire current-output DAC | 10.8 V to 40 V (AVDD) |
Separate local supply and ground; 0–20 mA, 4–20 mA, 0–24 mA programmable |
PLC analog output cards and high-power transmitters (> 3.6 mA) |
| AD5422BREZ | 3-wire / 4-wire current + voltage DAC | 10.8 V to 40 V (AVDD, bipolar AVSS optional) |
Separate local supply; selectable current (4–20 mA) and voltage (0–10 V, ±10 V) outputs |
Multi-mode industrial PLC modules needing tighter B-grade 0.01% TUE |
Inside the two-wire family itself, part-number suffixes alter calibration scaling: XTR115 provides an integrated 2.5 V reference while XTR116 provides 4.096 V (and XTR117 omits the integrated precision reference altogether so an external reference sets the span). All three enforce a 100:1 nominal input-to-output current gain, meaning a change from 2.5 V to 4.096 V shifts full-scale scaling by 63.8% unless the input scaling resistor network is recalculated. Similarly, tying local sensor ground to IO instead of IRET—a classic failure documented in TI’s two-wire transmitter application guide—bypasses the internal sense resistor and adds local quiescent current directly as output error.
When an external precision reference drives the front-end ADC and DAC chain, allocate reference initial accuracy, temperature drift, and dynamic settling separately using the voltage-reference ADC error-budget guide and the SAR ADC reference-settling validation procedure. Keep upstream sensor bridge errors isolated from loop-stage errors by following the RTD two-, three-, and four-wire error-budget methodology.
Pass-transistor thermal limits and qualification gates
Compliance testing covers the low-supply, high-load corner, whereas thermal stress peaks at the exact opposite corner: maximum loop supply voltage (V_LOOP_MAX, often 30 V to 36 V) with minimum external load resistance (R_LOAD_MIN, down to 0 Ω during a direct wiring short or 50 Ω on a local bench calibrator).
The power dissipated in the external NPN pass transistor (such as a BCP56 or FZT851 paired with XTR117) is:
P_PASS = (V_LOOP_MAX − V_REG_DROP − I_MAX × R_LOAD_MIN) × I_MAX
At V_LOOP_MAX = 36 V, R_LOAD_MIN = 0 Ω, and I_MAX = 22 mA fault current, the pass transistor absorbs nearly 0.79 W continuously (36 V × 0.022 A). Inside a sealed 85 °C industrial transmitter housing, a SOT-23 transistor with θJA = 200 °C/W would experience a +158 °C junction rise (T_J = 243 °C), destroying the device immediately. Sizing a SOT-223 or DPAK pass transistor with adequate copper pour (θJA ≤ 60 °C/W, giving T_J ≈ 132 °C < 150 °C max) keeps the pass stage inside its Safe Operating Area (SOA) and decouples self-heating away from the precision reference and front-end amplifier.
Before releasing a transmitter IC and its companion pass device for industrial automation component sourcing across Texas Instruments or Analog Devices portfolios, pass four bench gates:
- Brownout compliance gate: Verify linear
22.00 mAoutput within±0.05%atV_LOOP_MIN(19.2 V) across the maximum rated loop resistance (R_SENSE + R_WIRE + R_BARRIER). - Low-alarm floor gate: Confirm the output reaches
3.60 mA(or3.20 mA) at maximum operating temperature without regulator dropout or ADC reset. - Cold startup gate: Power up at
−40 °Cwith full capacitive load onV_REGand verify monotonic settling to the valid measurement band without latching into high alarm. - Short-circuit thermal soak: Hold
22 mAinto0 ΩatV_LOOP_MAXand maximum ambient temperature for 30 minutes while confirming pass-transistorT_Jstays below125 °Cand transmitter output drift stays inside spec.
Lock the transmitter IC, reference scaling resistors, pass transistor, and protection diodes together on the controlled BOM verification package so a purchasing alternate never alters compliance voltage or thermal headroom unnoticed.
Frequently Asked Questions (FAQ)
What loop resistance ceiling applies to a 24 V transmitter with a 7.5 V minimum terminal drop at 22 mA?
At a 19.2 V brownout (-20% on 24 V) and 22 mA NAMUR NE43 high-alarm current, total series resistance (R_SENSE + R_WIRE + R_BARRIER) cannot exceed (19.2 V - 7.5 V) / 0.022 A = 531.8 Ω. Any combined resistance above that threshold causes the loop to clip before reaching the fault state.
When should a design move from a two-wire transmitter to a three-wire current-output DAC?
Move to a three-wire architecture such as AD5420 or AD5422 whenever total sensor excitation, microcontroller, reference, and regulator quiescent current exceeds 3.2–3.5 mA, leaving insufficient margin below the 3.6 mA NAMUR NE43 low-alarm threshold.
Why must local electronics return to IRET instead of loop ground on an XTR115/XTR117 transmitter?
The internal current-sense loop regulates total current exiting IO relative to IRET. Routing local ground to IO bypasses the sense element, adding the entire electronics quiescent current directly as an uncalibrated output offset error.
Does a 250 Ω PLC receiver resistor work with intrinsic-safety Zener barriers on a 24 V supply?
Only if total loop impedance fits the brownout compliance equation. A 250 Ω sense resistor plus a 300 Ω Zener barrier and 100 Ω field cable drops 14.3 V at 22 mA, leaving only 4.9 V at 19.2 V supply—below the 7.5 V minimum required by XTR115/XTR117 transmitters unless the barrier impedance or sense resistor is reduced.